Casflo Sewage
Treatment Systems
Designed for
use where the installation of a septic tank is either unacceptable
or impractical and a connection to the main sewer impossible, the
CAMTECH CASFLO sewage treatment system offers an extremely efficient
and unobtrusive means of sewage disposal. Manufactured entirely
from robust and corrosion free Elite fabrication grade PROPYLEX,
the CAMTECH CASFLO incorporates unique and patented features to
ensure simplicity and efficiency of operation whilst being able
to consistently achieve the ever more stringent standards of discharge
effluent quality being required by the Environment Agency. Available
in a range of sizes to suit virtually any application from a single
residential property, hotels and restaurants or a major industrial
/ commercial complex, CAMTECH will design and manufacture a system
to meet the specific requirements of each individual situation.
PROCESS
DESCRIPTION
INFLUENT DESIGN PARAMETERS
|
| DWF
(Dry Weather Flow) |
=
Daily Flow as Detailed |
| Peak
Design Flow |
=
3 x DWF |
| Organic
Load |
=
As Detailed |
| Nature
of Influent |
=
CRUDE SEWAGE |
| PH
Range |
=
6 8 |
| Standard
Effluent Quality |
=
20mg/L BOD : 30mg/L SS |
| ALL
SURFACE WATER MUST BE EXCLUDED - NO WASTE DISPOSAL UNITS IN
USE, AN EFFECTIVE GREASE TRAP MUST BE INSTALLED ON ANY COMMERCIAL
KITCHEN DRAINS. eg.: HOTELS / RESTAURANTS |
Installation of
CASFLO sewage treatment systems requires no specialist equipment and
can be carried out by any competent contractor, quickly and simply.
Once installed, the CASFLO unit is completely unobtrusive, even the
largest systems.
By using only
the best and most reliable components and with no moving parts within
the unit,maintenance requirements and running costs are kept to
an absolute minimum. In recognition of increasing environmental
requirements, CAMTECH CASFLO sewage treatment systems undergo continual
development to improve process efficiency and cost effectiveness.
Whatever your requirement, CAMTECH will be pleased to provide all
design and regulatory approval assistance that may be needed for
any type of application. Please contact our technical department
for further details.
CASFLO
Package Sewage Treatment Plant
The
CASFLO treatment plant is of unitank design and incorporates
Primary Settlement (PST) Biological Treatment (Biozone), and Final
Settlement (FST) within the same structure, allowing delivery to
site as a complete unit to provide for a simple and straightforward
installation. No other tanks are required except for larger applications
( over 300 p.e. ) where a modular system is provided or where additional
treatment may be required to achieve more stringent effluent quality
standards or where effluent re-use is proposed. The CASFLO
Treatment plant has been designed to optimize the aesthetic qualities
of the final installation by ensuring that there is minimum visual
impact. The CASFLO process is designed in accordance
with the requirements of BS 6297.
Primary
Settlement Tank
The primary settlement tank is a two stage tank designed to maximize
the removal of gross and suspended solids prior to transfer of the
settled effluent to the biozone for treatment. The primary settlement
tank also incorporates for a sludge storage
volume (based on full load) depending on the desludge periods as
identified for individual applications.
Biozone
The biological treatment phase utilizes BAF technology (biological
aerated filter) which incorporates two proven principles of biological
process in the form of a fixed film reactor for process stability
and a suspended floc dispersed growth system for high transfer rates
and operational control, to ensure a stable treatment process which
is largely unaffected by shock loads. The process incorporates a
submerged, high rate, plastic media on which a fixed film of biomass
is grown. This film takes nutrition from the incoming settled effluent
and is provided with oxygen by means of a small blower unit which
aerates the media through HDPE membrane diffusers to provide fine
bubble aeration. The action of the fine bubble aeration is carefully
controlled to provide optimum oxygen transfer rates and to provide
a scouring action to slough off excess biomass to keep the thickness
of the fixed biological film at optimum levels, thereby preventing
the production of anaerobic bacteria and ensuring maximum process
efficiency. The fact that the media remains submerged allows for
an element of suspended floc dispersed growth which basically means
that there will be biomass which is unfixed to the media
but achieves treatment through suspended aeration.
The
biozone incorporates a two stage process as standard that allows
for constant mixing of incoming settled effluent to provide optimum
treatment stability and to avoid any short-circuiting.
The use of a two stage biozone ensures a high degree of process
efficiency to not only reduce B.O.D. levels to that required, but
will also achieve reductions in ammoniacal nitrogen in excess of
standard requirements.
Final Settlement
Tank
The final settlement tank is designed in accordance with the requirements
of BS 6297 to ensure relevant surface areas and rise rates are achieved
to provide maximum settlement of any suspended solids prior to discharge.
The CASFLO system also incorporates continuous and automatically
timed humus sludge return systems to return humus sludge from both
the final settlement tank and each biozone, back to the primary
settlement tank. Additionally this system also provides for continuous
recycling of treated effluent back to the P.S.T. to not only provide
dilution of incoming settled effluent but to also ensure continuous
flow during periods of low or no flow, thereby keeping the biomass
in prime condition.
Tertiary
Treatment Options
- Phosphate
Removal
- Sand Filtration
- UV Sterilization
- Effluent
Re-use

200pe
CASFLO Treatment Plant installed and ready for final landscaping
To maximize efficiency and to minimize maintenance requirements
and potential problems, there are NO mechanical or moving parts
contained within the treatment plant.
|